Impedance, phasors and power factor in AC circuits

Updated 28 Nov 2026 · 7 min read

In a DC circuit, resistance is enough. In an AC circuit the current and voltage can peak at different times, so the ratio needs both a magnitude and a phase. That is a complex number: Z = R + jX, with R the resistance and X the reactance. Inductive reactance is XL = ωL and capacitive reactance is XC = −1/(ωC).

The magnitude is |Z| = √(R² + X²) and the angle is φ = arctan(X/R). The current is I = V/Z. With V taken as the reference at 0°, a positive X makes the current lag by φ, and a negative X makes it lead.

Z = R + jX   ·   |Z| = √(R² + X²)   ·   φ = arctan(X/R)

A complete example

Let R = 6 Ω and X = +8 Ω at 60 Hz, so Z = 6 + j8 Ω. Then |Z| = √(36 + 64) = 10 Ω and φ = arctan(8/6) = 53.13°. With a 100 V RMS source, the current is 10 A RMS and lags the voltage by 53.13°. The power factor is cos 53.13° = 0.60 lagging.

The resistor voltage is IR = 60 V and the inductor voltage is IX = 80 V. They add as phasors at right angles: √(60² + 80²) = 100 V, matching the source. Adding them as ordinary numbers would give 140 V, which is the most common phasor mistake.

Three kinds of power

Real power, in watts, is what does work: P = VI cosφ. Reactive power, in volt-amperes reactive, shuttles energy between the source and the reactance without net work: Q = VI sinφ. Apparent power, in volt-amperes, is their vector sum: S = VI = √(P² + Q²).

For the example, P = 100 × 10 × 0.60 = 600 W, Q = 100 × 10 × 0.80 = 800 VAr and S = 1000 VA. The 800 VAr is not lost; it is exchanged with the source twice per cycle. It still requires current-carrying capacity, which is why cables and transformers are rated in VA and not in W.

The power triangle

Plot P horizontally, Q vertically and S as the hypotenuse. The angle between P and S is φ. Improving the power factor adds a negative Q (a capacitor) that cancels part of the positive Q, shrinking the vertical side and the hypotenuse while P stays the same. That is the whole idea of power-factor correction, and the next guide computes the capacitor.

A lagging power factor means current lags voltage, which is the inductive case: motors, transformers, fluorescent ballasts. A leading power factor means current leads, which is the capacitive case: over-compensated banks, long lightly loaded cables. Utilities usually penalise lagging power factor and may also penalise leading power factor at light load.

Phasor arithmetic in practice

To add two impedances in series, add the complex numbers: Z = Z₁ + Z₂. In parallel, add admittances: Y = Y₁ + Y₂ and then invert. Series and parallel rules are the same as for resistors, provided you keep the imaginary parts. Two 6 + j8 Ω impedances in parallel give (6 + j8)/2 = 3 + j4 Ω, because they are equal; unequal impedances require the full complex calculation.

The simulator's phasor diagram draws V, I and the reactive component at their actual angles, and the readouts give |Z|, ∠Z and the power factor. Change the power factor target and watch the current phasor rotate toward the voltage while its length falls.

The angle sign convention matters. With I = V/Z and V at 0°, a positive reactance gives a negative current angle. Some textbooks use the opposite convention for the phasor rotation; the physical statement 'current lags voltage in an inductor' does not change.

Questions

Does a low power factor waste energy?

It does not consume energy directly, but it increases the current needed for the same real power. Larger current means larger I²R losses in cables and transformers, larger voltage drop, and less capacity left for other loads. Utilities therefore charge for reactive power or penalise a low power factor.

Why is impedance complex?

Because a sinusoidal voltage and current can differ in both size and phase. A complex number carries both: its magnitude is the ratio of amplitudes, its angle is the phase difference. Resistance sets the real part, reactance the imaginary part.

The three-phase page draws the voltage and current phasors while you change the power factor.

Open the simulator

Written from standard electromagnetic theory and AC circuit analysis; the worked numbers can be reproduced in the simulator linked above.