Three-phase power uses three voltages of equal magnitude, 120° apart. In a star (wye) connection one end of each winding is joined at a neutral point; in a delta connection the windings form a closed triangle. The two connections give different relationships between phase and line quantities, and those relationships are where the √3 comes from.

In star, the line current equals the phase current and the line-to-line voltage is √3 times the phase voltage: VL = √3Vph. In delta, the line voltage equals the phase voltage and the line current is √3 times the phase current: IL = √3Iph. In both cases the total power is the same expression.

P = √3 V_L I_L cosφ   ·   S = √3 V_L I_L   ·   Q = √3 V_L I_L sinφ

A worked 380 V feeder

A balanced load draws 100 A per line at 380 V line-to-line with a power factor of 0.85 lagging. The apparent power is S = √3 × 380 × 100 = 65.8 kVA. The real power is P = 65.8 × 0.85 = 55.9 kW. The reactive power is Q = √(65.8² − 55.9²) = 34.6 kVAr, or directly √3 × 380 × 100 × sin(31.8°) = 34.6 kVAr.

The phase voltage in star is 219.4 V. Each phase carries 100 A and delivers 219.4 × 100 × 0.85 = 18.65 kW, and three phases give 55.9 kW. The arithmetic confirms that the √3 formula is just three phase powers added with the star voltage relationship substituted.

Where the √3 comes from

Take two line-to-neutral voltages 120° apart and subtract them to get the line-to-line voltage. The magnitude of the difference is 2Vphcos30° = √3Vph. The same geometry applies to currents in a delta. The factor is not a magic constant; it is the chord length of a 120° arc in the phasor diagram.

That also explains why the neutral current in a balanced star load is zero: the three phase currents are equal in magnitude and 120° apart, so their phasor sum is zero. Unbalanced loads produce a neutral current, which is why the neutral conductor must never be fused or switched alone in a four-wire system.

Delta and star loads

A heater rated for 380 V in delta can be reconnected in star and will see 219 V per element, so its power falls to one third. The reverse reconnection raises the power by three and usually destroys the element. Motor nameplates show both connections for this reason, and the terminal links must match the supply voltage.

For the same three impedances, a delta load draws three times the line current of the star connection, because each element sees √3 times the voltage and there are three of them across the lines. That is why star-delta starters reduce the starting current of a motor to one third, at the cost of one third of the starting torque.

Power measurement

A balanced three-phase load needs one wattmeter: measure one phase power and triple it. An unbalanced three-wire load needs two wattmeters, and the total is the sum of their readings; the sign of one reading can be negative at a low power factor, which is normal and not an error. Four-wire unbalanced loads need three wattmeters, one per phase.

The two-wattmeter method also gives the power factor: tanφ = √3(W₁ − W₂)/(W₁ + W₂). If both readings are equal, the power factor is 1. If one reads zero, it is 0.5. If one reads negative, the power factor is below 0.5. This is a quick field check that needs no phase-angle meter.

What the simulator computes

The three-phase page takes line voltage, load power, power factor, line impedance and length, and computes line current, apparent and reactive power, voltage drop, line loss and efficiency. Switch to single-phase and the same load needs a much larger current for the same power, which shows up immediately in the drop and loss readouts.

The formulas assume a balanced, sinusoidal system. Harmonics, unbalanced loads and neutral currents need per-phase or symmetrical-component analysis and are outside this model.

Questions

Is 380 V a phase voltage or a line voltage?

It is a line-to-line voltage. The corresponding line-to-neutral voltage in a star system is 380/√3 = 219.4 V, which is the 220 V nominal value used for single-phase loads. Saying '380 V three-phase' always means the line-to-line value.

Why is three-phase better than three separate single-phase circuits?

For the same power and the same conductor cross-section, three-phase uses less copper and gives constant instantaneous power instead of pulsating power. The constant power means smoother torque in motors and smaller vibration.

Switch between single-phase and three-phase and compare current, drop and loss for the same load.