Three-phase power, power factor and line drop

Enter a load, a feeder and a target power factor, and read apparent and reactive power, line current, the capacitor bank in kVAr and microfarads, voltage drop, line loss and efficiency — before and after correction.

  • V
  • I₁
  • I_C
  • I₂

Method

The model

Power and current

S = P/pf, Q = P tanφ, and I = P/(√3 V_L pf) for three-phase or P/(V pf) for single-phase. The capacitor bank is Q_c = P(tanφ₁ − tanφ₂).

Capacitance

For a three-phase bank, C_delta = Q_c/(3ωV_L²) and C_star = Q_c/(ωV_L²) per phase; for single-phase, C = Q_c/(ωV²). The star bank needs three times the microfarads because each capacitor sees V_L/√3.

Drop and loss

ΔV = √3 I L(R cosφ + X sinφ) for three-phase and 2 I L(R cosφ + X sinφ) for single-phase, with L in km and R, X in Ω/km. Loss is 3I²RL or 2I²RL. The model assumes a balanced sinusoidal load and a short line.

Formulas

Equations in use

S = P/pf, Q = P tanφ, P = √3 V_L I_L cosφ

Q_c = P(tanφ₁ − tanφ₂), C_Δ = Q_c/(3ωV_L²), C_Y = Q_c/(ωV_L²)

ΔV_3φ = √3 I L (R cosφ + X sinφ), P_loss = 3 I² R L

The dashed phasor is the current after correction. Watch the current angle close toward the voltage and the efficiency readout rise.