Voltage drop and line loss: the two costs of a long feeder

Updated 28 Nov 2026 · 7 min read

A feeder has resistance and reactance distributed along its length. Current through them produces a voltage drop at the load and a power loss in the conductor. Both grow with length and current, and both are reduced by a larger conductor or a higher supply voltage. The formulas below are the standard approximations for a short line, where shunt capacitance is neglected.

1φ: ΔV = 2 I L (R cosφ + X sinφ)   ·   3φ: ΔV = √3 I L (R cosφ + X sinφ)

Here I is the line current in amperes, L the one-way length in kilometres, R and X the conductor resistance and reactance in ohms per kilometre, and φ the load angle. The result is a line-to-neutral drop for single-phase and a line-to-line drop for three-phase.

Worked three-phase feeder

A 380 V feeder carries 100 A over 0.20 km with R = 0.08 Ω/km and X = 0.06 Ω/km at a power factor of 0.85. cosφ = 0.85 and sinφ = 0.527. The bracket is 0.08 × 0.85 + 0.06 × 0.527 = 0.0680 + 0.0316 = 0.0996 Ω/km. Then ΔV = √3 × 100 × 0.20 × 0.0996 = 3.45 V, which is 0.91 percent of 380 V.

The line loss is 3I²RL = 3 × 10 000 × 0.08 × 0.20 = 480 W. Against a delivered 55.9 kW that is 0.86 percent, so the efficiency is 99.1 percent. Both figures are comfortably within typical limits, which is why a 0.2 km feeder at this current is not usually a problem.

The same load, single-phase

Delivering 55.9 kW at 220 V single-phase needs I = 55 900/(220 × 0.85) = 299 A, roughly three times the three-phase current. With a two-wire loop the drop is 2 × 299 × 0.20 × 0.0996 = 11.9 V, or 5.4 percent, and the loss is 2 × 299² × 0.08 × 0.20 = 2.86 kW, five times larger. This is the practical reason three-phase distribution exists.

The comparison also shows why the current matters more than the voltage: loss goes as I², so tripling the current multiplies loss by nine before the conductor count is considered. Raising the distribution voltage reduces current for the same power and is the other lever.

The 3 percent rule and its limits

Many installations aim to keep the drop from the point of supply to the final load within about 3 percent for lighting and 5 percent for power, with the total including the service and the internal wiring. The exact figure is set by local code or by the equipment's tolerance, not by a universal law. Motors tolerate more drop at start, electronics tolerate less.

Voltage drop is not the only limit. Conductor ampacity, short-circuit withstand, earth-fault loop impedance and harmonic loading can each govern the size. A cable chosen only for drop may be thermally adequate but electrically noisy; a cable chosen only for ampacity may drop too much at the far end.

Reactance and power factor

For small cables at low voltage, R dominates and X can be neglected for a first estimate. For large cables, busbars and medium-voltage lines, X becomes comparable to R, and the reactive term can be half the drop at a power factor of 0.85. That is why power-factor correction reduces voltage drop even when the conductor is unchanged.

The power page shows both effects side by side: the drop and loss before correction, and the same quantities after a capacitor bank raises the power factor to the target. The current falls, the sinφ term falls, and the efficiency readout moves. Try a long feeder with a low power factor and watch the drop exceed 5 percent.

Checking a design

Compute the drop at full load and at the largest starting current, not only at nominal. Check the loss at the actual duty cycle rather than the peak, because a feeder that runs at 30 percent load most of the time has a much smaller annual loss than the peak figure suggests. Finally, verify the voltage at the far end with a meter after installation; calculated and measured values often differ by a few percent because of joints, temperature and actual conductor routing.

The formulas ignore shunt capacitance and skin effect. For lines longer than about 80 km at 50 or 60 Hz, or for fast transients, a distributed transmission-line model is required.

Questions

Why is the single-phase drop formula twice the three-phase one?

Single-phase current travels out on one conductor and back on the neutral, so the loop length is twice the run. Three-phase uses three conductors and the return path is the other two phases, so the factor is √3 rather than 2.

Does voltage drop depend on power factor?

Yes. The drop is I(R cosφ + X sinφ) per unit length, so a reactive load with the same current produces a larger drop than a resistive one. Correcting the power factor reduces both the current and the sinφ term.

Set the feeder length and conductor impedance, then compare efficiency before and after correction.

Open the simulator

Written from standard electromagnetic theory and AC circuit analysis; the worked numbers can be reproduced in the simulator linked above.