Power-factor correction: sizing a capacitor bank correctly
A lagging load needs reactive power to build magnetic fields. A capacitor supplies that reactive power locally instead of sending it down the line. The result is a smaller line current for the same real power, lower losses, lower voltage drop and more capacity in the transformer. The design question is how many kVAr to install.
The required reactive power is the difference between the reactive power at the present power factor and the reactive power at the target: Qc = P(tanφ₁ − tanφ₂), with φ₁ = arccos(pf₁) and φ₂ = arccos(pf₂). P is the real power in kW and Qc comes out in kVAr.
Q_c = P (tan φ₁ − tan φ₂) · C_star = Q_c·10³/(ωV_L²) · C_delta = Q_c·10³/(3ωV_L²)
The worked example
A 100 kW load at 0.85 lagging is to be corrected to 0.95 lagging. φ₁ = 31.79°, tan φ₁ = 0.6197. φ₂ = 18.19°, tan φ₂ = 0.3287. The difference is 0.2910, so Qc = 100 × 0.2910 = 29.1 kVAr.
At 380 V line-to-line and 60 Hz, ω = 377 rad/s. In delta, each capacitor sees 380 V, so C = 29 100/(3 × 377 × 380²) = 29 100/163 316 400 = 178 µF per phase. In star, each capacitor sees 219.4 V, so C = 29 100/(377 × 380²) = 535 µF per phase, three times larger. The stored reactive power is the same; the voltage per capacitor is not.
After correction the line current falls from 178.8 A to 160.0 A at 380 V. The cable loss, proportional to current squared, falls by about 20 percent. The apparent power falls from 117.6 kVA to 105.3 kVA, freeing 12.3 kVA of transformer capacity.
Star or delta
Delta is the usual choice for low-voltage banks because each capacitor is smaller and the loss of one capacitor only reduces the bank by one third rather than opening the neutral. Star banks are used where the capacitor voltage rating suits the phase voltage, and they allow a neutral connection for protection. The microfarad values are not interchangeable between the two.
Capacitor voltage rating must exceed the actual voltage with margin. A 440 V capacitor on a 380 V system is normal practice because it extends life and tolerates overvoltage; a 400 V capacitor on the same system has almost no margin and will fail early. Harmonic-rich systems need a higher rating still.
Steps, switching and over-correction
Real loads vary, so banks are switched in steps, typically 12.5 to 25 kVAr per step, controlled by a reactive-power relay. The relay measures the displacement power factor and switches steps to hold the target. Too few steps give coarse control; too many give frequent switching and contactor wear. Capacitor contactors include damping resistors to limit the inrush when a step is energised.
Over-correction makes the power factor leading. At light load a fixed bank can be larger than the load's reactive demand, and the excess reactive power flows back to the supply, raising voltage and sometimes attracting a leading-power-factor penalty. Automatic regulation and a target below unity avoid this.
The resonance trap
The capacitor bank and the supply transformer inductance form a parallel resonant circuit. The resonant frequency is fr = fsupply√(Ssc/Qc), where Ssc is the short-circuit capacity at the connection point. If fr coincides with a harmonic the load produces, typically the 5th or 7th, the bank magnifies that harmonic and can fail.
The usual fix is a detuned reactor in series with the capacitor, tuned below the lowest harmonic, typically to 189 Hz for a 50 Hz system (the 7th harmonic) or 227 Hz for 60 Hz. The reactor raises the capacitor voltage, so the capacitor rating must be adjusted. A bank that trips its fuses repeatedly is often a resonance problem, not a capacitor quality problem.
What to measure before and after
Record kW, kVAr, kVA, power factor, line current and voltage before correction, then again at the same load after. A 5 to 10 percent current reduction and a 15 to 25 percent loss reduction are typical for a correction from 0.85 to 0.95. Check the voltage rise: it is roughly ΔV/V ≈ QcX/V² and can push a lightly loaded system above its limit.
The simulator uses the ideal capacitor model with no losses or harmonics. A real bank has capacitor tolerances of ±5 to ±10 percent, discharge resistors, and a switching duty that the design must respect.
Questions
Can I correct to a power factor of 1.0?
Technically yes, but it is a bad idea. At unity the system is close to resonance with the supply inductance, and any load change makes the power factor leading. Most designs target 0.95 to 0.98 lagging, which captures nearly all the loss reduction with a safety margin.
Why does the capacitor value differ between star and delta?
Each capacitor sees a different voltage. In delta each one sees the full line voltage, so it stores more reactive power per microfarad; in star each sees the line voltage divided by √3, so three times the capacitance is needed for the same total kVAr.
Set a load of 100 kW at 0.85 and a target of 0.95, then read Qc and C for both connections.
Open the simulatorWritten from standard electromagnetic theory and AC circuit analysis; the worked numbers can be reproduced in the simulator linked above.